PRODUCT

Green Information and Communications Technologies

Surge protector (Din-rail type)

Surge protector (Din-rail type)

Kumsung SPD Series Surge Protector is used for power supply of low-voltage incoming panel lead-in and can be used in places with a high number of lightning strikes where it is hard to disperse the lightning strikes.

Features

Our Class ll Din-rail Surge Protector protects the power of devices or facilities from lightning surge and switching surge of an electrical system 220V/380V, low-voltage AC 50/60Hz.

MoV (metal oxide varistor) and GDT are built-in to prevent a fire on the surge protector when a leakage current increases by flames from lightning strikes.

The MOV is provided in a plug-in type, which is economic and good for maintenance (convenience) and installation in a small space.

The module-form protector shows green for normality and red for failure.

Usage

  • Protection for various power lines of distribution boards and panel boards
  • Protection for power supply of various devices and electronics
  • Compact-size good for installation in a small space
  • Easy maintenance and cost reduction (attached to rail)
  • Display window to show the operation status
  • Combined protection unit structure for enhanced performance

Specification of surge protector DIN-rail type

Type Single Phase 3-Phase Single Phase
Product Name

KS-S040DK

KS-S080DK

KS-T040DK

KS-T080DK

KS-S0104B

Rated Voltage

‘~’AC220V

‘~’AC220V

‘~’AC220V

‘~’AC220V

‘~’AC220V

Wiring

‘1P 2W + G

‘1P 2W + G

‘3P 4W + G

‘3P 4W + G

‘1P 2W + G

Maximum Continuous Voltage (UC)

‘~’50/60Hz

‘~’50/60Hz

‘~’50/60Hz

‘~’50/60Hz

‘~’50/60Hz

Maximum Continuous Voltage (UC)

320VAC

320VAC

320VAC

320VAC

320VAC

Voltage Protection Level (Up)

1.5kV/Peak

1.8kV/Peak

1.5kV/Peak

1.8kV/Peak

1.5kV/Peak

Nominal Discharge Current (In)

20kA

40kA

20kA

40kA

20kA

Maximum Discharge Current (max)

40kA

80kA

40kA

80kA

160kA

Protection Grade

Class Ⅱ

Class Ⅱ

Class Ⅱ

Class Ⅱ

Class Ⅱ

Leakage Current

Within 1mA

Within 1mA

Within 1mA

Within 1mA

Within 1mA

Rated Short-Circuit Current

1.5kA

1.5kA

1.5kA

1.5kA

1.5kA

Installation Place

Indoors

Indoors

Indoors

Indoors

Indoors

No. of Port

1 port

1 port

1 port

1 port

1 port

Installation Structure

TN,TT

TN,TT

TN,TT

TN,TT

TN,TT

Connection Method

Screw terminal and bolt connection

Screw terminal and bolt connection

Screw terminal and bolt connection

Screw terminal and bolt connection

Screw terminal and bolt connection

Mounting Method

Screw attachment method

Screw attachment method

Screw attachment method

Screw attachment method

Screw attachment method

External Dimension (mm)

36(W)*90(H)*70(D)

48(W)*90(H)*70(D)

72(W)*90(H)*70(D)

96(W)*90(H)*70(D)

40(W)*84(H)*65(D)

Temperature & Humidity Range

-40℃~+70℃/5%~90%

-40℃~+70℃/5%~90%

-40℃~+70℃/5%~90%

-40℃~+70℃/5%~90%

-40℃~+70℃/5%~90%

Surge Life

In20kA / 15 Pulse

Imax40kA / 2 Pulse

In40kA / 15 Pulse

Imax80kA / 2 Pulse

In20kA / 15 Pulse

Imax40kA / 2 Pulse

In40kA / 15 Pulse

Imax80kA / 2 Pulse

In20kA / 15 Pulse

Imax40kA / 2 Pulse